Options
Experimental investigation of power quality disturbances associated with grid integrated wind energy system
Date Issued
2017-08-22
Author(s)
Venkatraman, Ashwin
Paduru, Kandarpa Sai
Mahela, Om Prakash
Shaik, Abdul Gafoor
DOI
10.1109/ICACCS.2017.8014686
Abstract
This paper presents the experimental investigation of power quality (PQ) disturbances associated with the grid integrated wind energy generator. PQ disturbances associated with the grid synchronization and outage of doubly fed induction generator (DFIG) based wind energy generation system have been investigated in the presence of various types of loads. The voltage signal has been captured at point of common coupling (PCC) using the data acquisition system consisting of power quality analyser, laptop, and WT viewer software. The voltage signal has been analysed using MATLAB software to find the PQ disturbances. It has been observed that the PQ disturbances such as voltage fluctuations, flicker, voltage sag, voltage swell and harmonics are associated with the grid synchronization and outage of DFIG based wind energy conversion system.