CVT Failures and Impact on Synchrophasor based Dynamic Monitoring
Date Issued
2023-01-01
Author(s)
Singh, Shaily
Yadav, Ravi
DOI
10.1109/CERA59325.2023.10455700
Abstract
Device malfunctions and instrument failures in a power system cause multi-component tripping, prolonged disruptions, and operational irregularities. The high voltage instrument transformers like capacitive voltage transformers (CVTs) are bound to maloperations/failures due to switching transient over-voltages, bushing failure, filter malfunctions, saturation of intermediate voltage transformer, etc. Among these failures, the transient over-voltages induce a ferro-resonance phenomenon in the CVTs, which could impact the phasor measurement accuracy at the synchrophasors. This paper presents a detailed sensitivity analysis of the frequency response of CVT with model parameter changes and discusses the impact of filter failures on the phasor measured at the synchrophasor. The analysis provides a detailed study of CVT frequency response and ferro-resonance phenomenon with a brief impact analysis on phasor measurement and associated applications. The propositions are tested with simulated detailed CVT models in Matlab/Simulink, where we observed predominant oscillatory dynamics in phasor measurements similar to sub-synchronous resonance making distinction and detection challenging.